Oil Purification products
Air Compressor Filter
Air Compressor Inline Filter
Water purification equipment
Air Purification Products
Brand Name: 无
Model Number: LFZ-600-300
Nominal filtration rating:≥300μm(筛网)
Application:冷却塔循环水、工业循环水预处理
Operating pressure:
Working temperature: ≤80℃
Replacement or not:Replacement
Water Filter Element line pairs consumable cartridges with complete pre-treatment equipment, and the LFZ-600-300 automatic brush self-cleaning filter is the large-flow brush unit under Water Filter Element. Working pressure 0.2-2.5 MPa, operating temperature ≤80 ℃, 380V 50Hz, backwash water consumption ≤2%, filtration precision 50-5000 μm, brush-type cleaning with 60s or adjustable cycle, manual or automatic control. LFZ-600-300: DN300, tank φ600×1750, 1.0 MPa, 0.75 kW, flow 550 m³/h, screen ≥300 μm.
| Model | LFZ-600-300 |
| Inlet / outlet | DN300 |
| Casing size | φ600 × 1750 mm |
| Pressure | 1.0 MPa |
| Motor power | 0.75 kW |
| Flow rate | 550 m³/h |
| Screen precision | ≥300 μm |
| Screen material | 304 / 316L / 2205 stainless steel |
| Cleaning method | Brush type, 60 s or adjustable |
| Control mode | Manual / automatic (time or differential pressure) |
Open cooling towers collect wind-blown dust, algae and scale particles that block heat-exchanger nozzles over a season. The automatic brush filter sits on the circulating return line: water passes the stainless screen, a motor-driven brush scrapes captured debris during a 60-second cycle, and drain water purges to waste without stopping the fan. LFZ-600-300 at DN300 and 550 m³/h matches a mid-size tower loop; larger plants step up to LFZ-700-350 (700 m³/h) or LFZ-800-400 (1000 m³/h). Downstream fine protection pairs the unit with a High Flow Filter Cartridge when process water demands lower turbidity.
Brush cleaning removes cake without cartridge replacement, so consumable cost drops to near zero for coarse dust. Backwash consumption stays ≤2% of flow, and the 60 s adjustable cycle plus differential-pressure trigger avoids wasted water. Screen materials 304, 316L or 2205 match normal, corrosive and seawater-influenced loops, and the tank can be Q235B, 304, 316L or rubber-lined carbon steel. Automatic control runs unattended, protecting heat-exchanger nozzle lifetime.
Our workshop assembles and pressure-tests each LFZ unit before dispatch, with brush, screen and valve spares supplied separately for long-term maintenance. Series flow covers LFZ-600-300, LFZ-700-350 and LFZ-800-400 for tower-to-pipeline scales. Custom screen mesh and tank material are quoted against water quality; for sizing support, contact our engineering team. The oil-side automatic filtration counterpart is referenced at Industrial Oil Purification Equipment.
Q1: Does brush cleaning need the loop to shut down?
A1: No. The cleaning cycle runs online; only a short drain purge occurs, fan and pumps keep running.
Q2: What screen precision suits cooling tower dust?
A1: ≥300 μm is typical for wind-blown dust and algae; choose finer mesh for process-sensitive heat exchangers.
Q3: Can it handle seawater-influenced cooling water?
A1: Select 316L or 2205 screen and rubber-lined or stainless tank; standard carbon steel is not for continuous chloride duty.
Q4: How is the cleaning cycle triggered?
A1: By fixed timer or inlet-outlet differential pressure, selected in the automatic controller; manual mode is available for maintenance.
Q5: What spare parts are stocked?
A1: Brush assembly, screen cylinder, solenoid valve and controller module are supplied as separate spares for site maintenance.
Reference: GB/T industrial automatic self-cleaning water filter specification